PIP | PIQ | PIPZ SERIES

POLYLUX’S PIP | PIQ | PIPZ SERIES

Single phase transformers designed to feed pool spotlights.

These series are made up of single-phase isolating transformers with a 12V output voltage that have a rating range as from 100VA up to 600VA. They are provided with a copper shield between primary and secondary, providing total safety for people against electrical risks.

Its main application is the supply of halogen spotlights in swimming pools and gardens and can be used as control transformers in installations with danger of electrical contact for people.

Constructive features:

  • Important note: copper shield between primary and secondary with connection to ground screw that prevents shunt voltage crossovers to the secondary circuit, thus posing no electrical risks for persons.
  • Connection terminals made of copper, welded and inserted in blocks to prevent hazards caused by expansion that may lead to poor connection.
  • Bridges for the different connections included in the product packaging.

PIP
Single-phase dry type isolation transformers, finished in anti-flash varnished in IP20 enclosure with copper screen between primary and secondary and protection to prevent direct contact with electrical parts.
Rating
From 100 VA to 600 VA
Input voltage
230 V
Output voltage
12,5 – 13 – 13,5 V
Protection degree
IP-20
Frequency
50/60 Hz
Cooling
ANAN
Ambient temperature
45 ºC
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
3 kV (1 min, 50 Hz)
Standards
IEC/EN/UNE-EN 61558, CE
Mounting
From DIN Rail and screws to Screws
PIQ
Single-phase dry type isolation transformers, finished in anti-flash varnished in IP20 enclosure resin filled, copper screen between primary and secondary and protection against direct contact with electrical parts.
Rating
From 100 VA to 600 VA
Input voltage
230 V
Output voltage
12,5 – 13 – 13,5 V
Protection degree
IP-20
Frequency
50/60 Hz
Cooling
ANAN
Ambient temperature
45 ºC
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
3 kV (1 min, 50 Hz)
Standards
IEC/EN/UNE-EN 61558, CE
Mounting
From Screws and DIN Rail to Screws
PIN
Single-phase dry type cast resin isolation transformers, IP20 with copper screen between primary and secondary and protection to prevent direct contact with electrical parts.
Rating
From 100 VA to 600 VA
Input voltage
230 V
Output voltage
12,5 – 13 – 13,5 V
Protection degree
IP-20
Frequency
50/60 Hz
Cooling
AN
Ambient temperature
45 ºC
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
3 kV (1 min, 50 Hz)
Standards
IEC/EN/UNE-EN 61558, CE
Mounting
From Screws and DIN Rail to Screws
PIPZ
Single-phase cast resin isolation transformers in IP54 enclosure, finished in anti-flash varnished to supply halogen spotlights for swimming pools and gardens with copper screen between primary and secondary.
Rating
From 100 VA to 600 VA
Input voltage
230 V
Output voltage
12,5 – 13 – 13,5 V
Protection degree
IP-54
Frequency
50/60 Hz
Cooling
ANAN
Ambient temperature
45 ºC
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
3 kV (1 min, 50 Hz)
Standards
IEC/EN/UNE-EN 61558, CE
Mounting
Screws

Special Manufacturing

We build transformers and inductive elements tailored to your needs.

Tell us about your needs and our engineers will create a solution adapted to your company.