RTOX | FTOX FAMILY

Reactors for harmonics filtering in three phase lines at the output of a converter

FTOX

Reactor

Anti-flash varnish finish, offering:

  • Protection against corrosive environments
  • Increase of electrical isolation
  • High compression capacity
  • Reduction of noise level
  • Increase of product's lifespan

Maximum output voltage 2Un (800V)

​Safety class I

Includes thermal protection against overtemperatures

Possibility of tailor-made manufacturing

Technical remarks about the use of line reactors:

  • Attenuation of voltage peaks in the output of the converter, protecting against premature degradation of the dielectrical parts of the motor
  • Reduction of the reflection effect due to the length of the cables between the converter and the motor. This effect amplifies voltage values in the terminals of the motor
  • It is recomended to use these inductances for lengths over 50 m from the converter to the motor

Showing 1 to 4 of 24 (6 pages)

FTOX2.5

2,5 A
0,75 kW / 1 CV
380 - 460 V
8,821 mH (50 Hz)
3% (50 Hz)
0,05
50/60 Hz
IP-00
AN
40ºC
Class F
Class F - 155ºC
Class HC - 220ºC
3 kV (1 min, 50 Hz)
IEC/EN/UNE-EN 60076-6, CE
Screws
2,3 kg
150x180x185x49x100 mm 6Ø

FTOX4

4 A
1,1 kW / 1,5 CV
380 - 460 V
5,513 mH (50 Hz)
3% (50 Hz)
0,05
50/60 Hz
IP-00
AN
40ºC
Class F
Class F - 155ºC
Class HC - 220ºC
3 kV (1 min, 50 Hz)
IEC/EN/UNE-EN 60076-6, CE
Screws
3,5 kg
150x190x185x59x100 mm 6Ø

FTOX5

5 A
1,5 kW / 2 CV
380 - 460 V
4,411 mH (50 Hz)
3% (50 Hz)
0,05
50/60 Hz
IP-00
AN
40ºC
Class F
Class F - 155ºC
Class HC - 220ºC
3 kV (1 min, 50 Hz)
IEC/EN/UNE-EN 60076-6, CE
Screws
3,6 kg
150x190x185x59x100 mm 6Ø

FTOX6.3

6,3 A
2,2 kW / 3 CV
380 - 460 V
3,501 mH (50 Hz)
3% (50 Hz)
0,05
50/60 Hz
IP-00
AN
40ºC
Class F
Class F - 155ºC
Class HC - 220ºC
3 kV (1 min, 50 Hz)
IEC/EN/UNE-EN 60076-6, CE
Screws
3,7 kg
150x190x185x59x100 mm 6Ø
Showing 1 to 4 of 24 (6 pages)