¿How to protect a transformer ?

The transformer must be protected against possible overcurrents or short circuits that may occur in the electrical grid, thus guaranteeing the correct operation of the installation, avoiding failures and their destruction.

The effectiveness of protections in transformers is essential to minimize the damage caused by faults of the transformer itself, and to avoid short circuits and overloads of external origin.  

Primary -> Against short circuits: The protections must be dimensioned according to the inrush current

Secundario -> Against overloads: The protections are dimensioned at the nominal current (In) as maximum 

Inrush current

PRIMARY

SECONDARY

<=12In

1.5÷2xIn curve D o fuse gL

In curve C or fast fuse gR

<=8In

In curve D o fuse gL

In curve C or fast fuse gR

<=5In

In curve C o fuse gL

In curve C or fast fuse gR

*In = Rated current (A)

The nominal value must be less than or  equal to that obtained from the calculation of the nominal current of the transformer

SINGLE-PHASE: In = Nominal power / Nominal voltage

THREE-PHASE: In= Nominal power / ( √3 *Nominal voltage)

All transformers manufactured by POLYLUX have an inrush current <=12In since high quality magnetic cores are used and the degree of compaction is high. 