SERIE TMTX | TMTW | TMTE

POLYLUX’S SERIE TMTX | TMTW | TMTE

Three phase transformers designed to adapt the voltage for measurement equipments.

The TMT series is made up of three-phase measuring transformers that includes a rating range as from 15VA up to 400VA and are intended to adapt the voltage for measurement equipment.

Its function is to provide a precise voltage at the output, isolating it from the input. On the one hand, it is possible to reduce the voltage to a lower high-precision value and, on the other hand, it is possible to isolate the high-voltage circuit from the measurement circuit.

Constructive features:

  • Connection terminals made of copper, welded and inserted in blocks to prevent hazards caused by expansion that may lead to poor connection.
  • Built with independent circuits for the three phases to obtain a perfect balance between them and guarantee precision in measuring.

TMTW
Three-phase dry type isolation measuring transformers, finished in anti-flash varnished in IP20 metal enclosure with protection to prevent direct contact with electrical parts.
Rating
From 15(Cl.0,2)-30(Cl.0,5)-50(Cl.1)VA to 200(Cl.0,2)-300(Cl.0,5)-400(Cl.1)VA
Input voltage
100..500 V
Output voltage
100..110 V
Protection degree
IP-20
Frequency
50/60 Hz
Connection group
Dd0/Dyn11/Dyn5/Yd5/Yyn0/Yzn11/Dzn0/Ynyn0
Cooling
ANAN
Ambient temperature
45 ºC
Thermal rating
6 times nominal rating
Overvoltage
1,2 times nominal voltage
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
3 kV (1 min, 50 Hz)
Standards
IEC/EN/UNE-EN 61869-3, CE
Mounting
Screws
TMTE
Three-phase dry type cast resin isolation measuring transformers for high corrosion and vibration environments.
Rating
From 15(Cl.0,2)-30(Cl.0,5)-50(Cl.1)VA to 200(Cl.0,2)-300(Cl.0,5)-400(Cl.1)VA
Input voltage
100..500 V
Output voltage
100..110 V
Protection degree
IP-20
Frequency
50/60 Hz
Connection group
Dd0/Dyn11/Dyn5/Yd5/Yyn0/Yzn11/Dzn0/Ynyn0
Cooling
AN
Ambient temperature
45 ºC
Thermal rating
6 times nominal rating
Overvoltage
1,2 times nominal voltage
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
3 kV (1 min, 50 Hz)
Standards
IEC/EN/UNE-EN 61869-3, CE
Mounting
Screws
TMTX
Three-phase dry type isolation measuring transformers with anti-flash varnish finished for maximum protection, insulation, noise and vibration reduction.
Rating
From 15(Cl.0,2)-30(Cl.0,5)-50(Cl.1)VA to 200(Cl.0,2)-300(Cl.0,5)-400(Cl.1)VA
Input voltage
100..500 V
Output voltage
100..110 V
Protection degree
IP-00
Frequency
50/60 Hz
Connection group
Dd0/Dyn11/Dyn5/Yd5/Yyn0/Yzn11/Dzn0/Ynyn0
Cooling
AN
Ambient temperature
45 ºC
Thermal rating
6 times nominal rating
Overvoltage
1,2 times nominal voltage
Temperature rise
Class B – 130ºC
Insulation
Class H – 180ºC
Windings
Class HC – 200 ºC
Test voltage
3 kV (1 min, 50 Hz)
Standards
IEC/EN/UNE-EN 61869-3, CE
Mounting
Screws

Special Manufacturing

We build transformers and inductive elements tailored to your needs.

Tell us about your needs and our engineers will create a solution adapted to your company.