Current transformers - TIP

Features

Measuring transformers

The short circuit on terminals or the connection to earth can be achieved by the double fast-on or connecting two wires on the same terminal.

Protection transformers

The C.T. when used as a current generator for protection relays has electrical characteristics which differ from those of the measuring transformer.

In fact, the measuring C.T. is expected to give a saturation of the magnetic circuit with 5P in primary currents, while in the case of protective C.T., it is necessary for the secondary current value to follow the increase in the primary current up to 10-15-20In, so as to guarantee the intervention of the relay in the case of unforeseen breakdown current.

It is important not to load the C.T. with a P performance which is greater than that indicated, so as not to modify the saturation value of the C.T.

P=R∗I2

P = Load on the C.T.

R = Resistance of the relay and resistance of the cables

I = Nominal secondary current of the C.T.

Applications

Available accessories

Downloads

TIP40A » TIP50A » TIP100A » TIP150A » TIP200A » TIP250A » TIP300A » TIP400A » TIP500A »
Input current 40 A 50 A 100 A 150 A 200 A 250 A 300 A 400 A 500 A
Output current 5 A 5 A 5 A 5 A 5 A 5 A 5 A 5 A 5 A
Class 3 3 1/3 0,5 / 1 / 3 1 / 3 1 / 3 0,5 / 1 / 3 0,5 / 1 / 3 0,5 / 1 / 3
Rating 1 VA 1,5 VA 2,5 VA / 5 VA 2 VA / 5 VA / 10 VA 4 VA / 8 VA 6 VA / 12 VA 6 VA / 8 VA / 12 VA 6 VA / 10 VA / 12 VA 6 VA / 10 VA / 12 VA
Frequency 50 – 60 Hz 50 – 60 Hz 50 – 60 Hz 50 – 60 Hz 50 – 60 Hz 50 – 60 Hz 50 – 60 Hz 50 – 60 Hz 50 – 60 Hz
Thermic short circuit current 40 IpN 1 seg. 40 IpN 1 seg. 40 IpN 1 seg. 40 IpN 1 seg. 40 IpN 1 seg. 40 IpN 1 seg. 40 IpN 1 seg. 40 IpN 1 seg. 40 IpN 1 seg.
Dynamic short circuit current 2,5 I th 1 seg. 2,5 I th 1 seg. 2,5 I th 1 seg. 2,5 I th 1 seg. 2,5 I th 1 seg. 2,5 I th 1 seg. 2,5 I th 1 seg. 2,5 I th 1 seg. 2,5 I th 1 seg.
Permanent overloading 120% Icth 120% Icth 120% Icth 120% Icth 120% Icth 120% Icth 120% Icth 120% Icth 120% Icth
Insulation In air, Class E In air, Class E In air, Class E In air, Class E In air, Class E In air, Class E In air, Class E In air, Class E In air, Class E
Test voltage 3kv (50Hz) 1 min. 3kv (50Hz) 1 min. 3kv (50Hz) 1 min. 3kv (50Hz) 1 min. 3kv (50Hz) 1 min. 3kv (50Hz) 1 min. 3kv (50Hz) 1 min. 3kv (50Hz) 1 min. 3kv (50Hz) 1 min.
Protection degree IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30 IP30
Ambient temperature -20ºC a 40ºC -20ºC a 40ºC -20ºC a 40ºC -20ºC a 40ºC -20ºC a 40ºC -20ºC a 40ºC -20ºC a 40ºC -20ºC a 40ºC -20ºC a 40ºC
Standards EN 61869-2 EN 61869-2 EN 61869-2 EN 61869-2 EN 61869-2 EN 61869-2 EN 61869-2 EN 61869-2 EN 61869-2
Mounting Screws and DIN rail Screws and DIN rail Screws and DIN rail Screws and DIN rail Screws and DIN rail Screws and DIN rail Screws and DIN rail Screws and DIN rail Screws and DIN rail
Weight 0,3 kg 0,3 kg 0,3 kg 0,3 kg 0,5 kg 0,7 kg 0,7 kg 1 kg 1 kg
Dimensions (AxBxCxDxE) 58x70x97 mm 58x70x97 mm 58x70x97 mm 58x70x97 mm 75x70x109 mm 75x70x109 mm 75x70x109 mm 105x85x131 mm 105x85x131 mm
Quote / Buy Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote Add to quote
How to buy?

You can buy online if you are located in one of this countries: Austria, Croatia, Czech Republic, Finland, France, Germany, Greece, Hungary, Ireland, Italy, Lithuania, Luxembourg Poland, Slovakia and Sweden.

Related series

TIB PRIMARY WINDING CURRENT TRANSFORMERS.
TIB
Rating
3 VA / 6 VA
Protection degree
IP30
TIN OPEN CORE CURRENT TRANSFORMERS.
TIN
Rating
From 1,5 VA / 3 VA / 10 VA to 8 VA / 17 VA / 30 VA
Protection degree
IP30

Special fabrications

We build transformers and inductive elements tailored to your needs.

Explain your needs and our engineers will create a solution adapted to your company.