TRFA2.5

Technical characteristics


Rating
2,5 Adc
Input voltage
230 Vac
Output voltage
12 Vdc
Output ripple
5%
Frequency
50/60 Hz
Protection degree
IP-20
Cooling
AN
Ambient temperature
25ºC
Temperature rise
Class B
Insulation
Class B - 130ºC
Windings
Class HC - 200 ºC
Test voltage
3 kV (1 min, 50 Hz) pri-sec 3 kV (1 min, 50 Hz) pri-earth 0,5 kV (1 min, 50 Hz) sec-earth
Standards
IEC/EN/UNE-EN 61204, CE
Mounting
Screws and DIN Rail
Weight
1,5 kg
Dimensions (AxBxCxDxE)
148x96x99 mm 6Ø

Applications


Rectifier transformer dry type encapsulated in resin with filter output:

  • Protection against corrosive environments.
  • Protection against high levels of vibrations.
  • Protection against electrodynamic efforts.
  • Reduction of the noise level.
  • Increase of the useful life of the product.

Safety class I.

Includes LED operation indicator and fuse starting at 300W.

Possibility of custom manufacturing if the standard specifications are not required.

Ripple voltage of approximately 5%

  • TRF rectifier transformers are used in applications where loads require DC power.

Available accessories

  • Fuse in primary

Plan